Mitsubishi Heavy Industries FDR508-A Specifikace Strana 8

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 51
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 7
534
FDR-H
Item
Model
FDR408-A FDC408HES3
Decorative panel
Panel model (Option)
Nominal cooling capacity
(1)
W 10000
Nominal heating capacity
(1)
W 11200
Power source 3 Phase, 380/415V, 50Hz
Cooling input kW 4.48/4.58
Running current (Cooling) A 7.6/7.9
Power factor (Cooling) % 90/81
Heating input kW 3.86/3.90
Running current (Heating) A 6.9/7.3
Power factor (Heating) % 85/74
Inrush current A 53
Noise level dB(A) 54
Exterior dimensions
mm 1250 × 920 × 340
Height × Width × Depth
Net weight kg 90
Refrigerant equipment
GU-A5550ES41 × 1
Compressor type & Q’ty
Motor kW 2.8
Starting method Line starting
Heat exchanger Louver fines & inner grooved tubing Slitted fines & bare tubing
Refrigerant control Capillary tube
Refrigerant R22
Quantity kg Holding charged
1.7 [Pre-charged up to the piping length of 5m]
Refrigerant oil r 1.6 (BARREL FREEZE 32SAM)
Defrost control MC controlled de-icer
High pressure control High pressure switch
Air handling equipment
Multiblade centrifugal fan × 3 Propeller fan × 2
Fan type & Q’ty
Motor W 45 × 1 + 90 × 1 40 × 2
Starting method Line starting
Air flow (Standard) CMM Hi: 28 Lo: 22 70
Available static pressure Standard: 50 (5.0) High: 80 (8.0)
Fresh air intake Available
Air filter, Q’ty Polypropylene net × 3 (washable)
Shock & vibration absorber Rubber sleeve (for fan motor) Rubber mount (for compressor)
Electric heater W 70 (Crank case heater)
Operation control Wired remote control switch
Operation switch (Optional : RCD-H-E) — (Indoor unit side)
Room temperature control Thermostat by electronics
Safety equipment
Internal thermostat for fan motor. Internal thermostat for fanmotor.
Frost protection thermostat. Abnormal discharge temperature protection.
Installation data mm
Liquid line: φ9.52 (3/8) Gas line: φ19.05 (3/4)
Refrigerant piping size (in)
Connecting method Flare piping
Drain hose (Connectable with VP25)
Insulation for piping Necessary (both Liquid & Gas lines)
Accessories Mounting kit, Drain hose
Optional parts Decorative Panel
Model FDR408HES-SA
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz.
(4) Canvas panel is used in combination with following canvas duct. Canvas duct: HA01503
(5) Main unit height of canvas specification type is higher than the other type for canvas duct portion.
Notes (1) The data are measured at the following conditions.
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling 27˚C 19˚C 35˚C 24˚C
Heating 20˚C 7˚C 6˚C
ISO-T1, JIS B8616
Operation data
(3)
Silent panel
R-PNLS-46W-E
Canvas panel
R-PNLC-46W-E
_
_
Hi: 45 Lo: 38 Hi: 46 Lo: 39
Unit: 406 × 1370 × 635
Panel: 10 × 1660 × 750
Unit: (350) × 1370 × 635
Panel: 10 × 1484 × 585
Unit: 50 Panel: 9 Unit: 50 Panel: 7
Pa
(mmAq)
FDR408HES-SA