6.3 Diagnosing of microcomputer circuit
(1) Selfdiagnosis function
(a) Indoor unit side
Error Code
Failure at: Contents of the failure
Defective connection or broken wire for control switch signal wire.
Signal noise has entered the control switch wire.
Is the circuit board for the control switch or the circuit board for the indoor unit is defective
(communication circuit defective)?
Indoor unit heat exchanger thermistor defective (element defective or broken wire). Defective
connection of connector for thermistor.
Indoor unit return thermistor defective (element defective or broken wire). Defective connection
of connector for thermistor.
Indoor unit heat exchanger thermistor defective (short circuit).
Indoor unit circuit board defective (defective thermistor input circuit)?
Indoor unit circuit board defective (defective thermistor input circuit)?
Indoor unit circuit board defective (defective thermistor input circuit)?
Heating overload (temperature of heat exchanger for indoor unit abnormally high)
Indoor unit heat exchanger thermistor defective (short circuit).
Indoor unit circuit board defective (defective thermistor input circuit)?
Failure with the condensate pump (DM), or open circuit or disconnection of connector with the condensate pump.
Malfunctioning of the float switch (erroneous functioning)
Indoor unit circuit board defective (defective float switch input circuit)
Indoor unit circuit board defective (defective DM driving output circuit)
1 Remote controller for multiple unit control, 17 or more indoor units connected
Gas leak.
E1
E6
E7
E8
E9
E57
E10
Control switch wire
(signal noise)
Circuit board for control
switch or indoor unit
Indoor unit heat exchanger
thermistor
Indoor unit circuit board
Indoor unit air inlet thermistor
Indoor circuit board
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Indoor unit circuit board
Installation and operating conditions
Indoor unit heat exchanger thermistor
Indoor unit circuit board
Failure in drainage
Float switch
Number of indoor units connected
Insufficient refrigerant
Table of inspection items based on error codes
(2) Error diagnosis procedures at the indoor unit side
To diagnose the error, measure the voltage (AC, DC), resistance, etc. at each connector around the circuit board of indoor unit
based on the inspection display or the operation state of unit (no operation of compressor or blower, no switching of 4-way valve,
etc.). If any defective parts are discovered, replace with the assembly of parts as shown below.
(a) Single-unit replacement parts for circuit board of indoor unit. (Peripheral electric parts for circuit board.)
Indoor unit printed circuit board, thermistor (return, heat exchanger), operating switches, limit switches,
transformers, fuses.
Note (1) Use normal inspection methods to determine the condition of strong electrical circuits and frozen cycle parts.
(b) Replacement procedure of indoor unit microcomputer printed circuit board
Microcomputer printed circuit board can be replaced with following procedure.
(i) Confirm the parts numbers. (Refer to the following parts layout drawing for the location of parts number.)