Parts layout on the indoor unit PCB
Model: FDT, FDR, FDUR series
•Function of DIP switched (SW3)
Switch Function
SW3-1
ON Power off guaranteed
OFF No power off guaranteed
ON With low-voltage detection
control
SW3-2
OFF Without low-voltage detection
control
SW3-3
ON Power up mode (UHi-Lo)
OFF Mild mode (Hi-Lo)
ON Indoor fan is Lo when heating
thermostat is OFF.
SW3-4
OFF Indoor fan is OFF when
heating thermostat is OFF.
(ii) Please match the settings of control switching switches (SW3, SW4, SW5) to the settings they had before they were
replaced. With these switches, if the printed circuit had a jumper wire before being replaced, set to jumper wire ON if
there was a jumper wire and jumper OFF is these was not.
(iii) Connect the fast-on terminals and connectors that are to the circuit board for the micro-computer.
Connect by matching the wire color of the fast-on terminal with the color printed on the circuit board for the micro-
computer.
Note (1) When connecting to the fast-on connection for the circuit board for the micro-computer, use care so as not to excessively distort the circuit
board.
(c) Inspection method when error code is displayed
Power supply connector
for PCB
Transformer, secondary side External input /
output function
SW4
SW5
SW3
SW1
SW2 (Only case of FDT)
(Optional : For auto lift panel)
( )
Indoor unit number
address switch
( )
For test mode selection
(Shortcircuit : Test mode)
Thermistor
(Return air)
Thermistor
(Heat exchanger)
Transformer, primary side
Power
supply
52X6
52X5 52X4 52X7 52X1 52X2 52X3
CNTCNV
SW4
SW2
SW5
CNE
CNQCNS CNH CNN
SW3
9
1011
76 3 48 13
SW1
•Function of DIP switched (SW4, 5)
Switch Function
SW4-1(J1)
ON Antifrost 2.5˚C
OFF Antifrost 1˚C
SW4-2(J2)
ON With abnormality resetting
OFF Without abnormality resetting
SW4-3(J3)
ON 4 position louver control: valid
OFF 4 position louver control: invalid
SW5-1(J4)
ON 1 Phase model
OFF 3 Phase model
SW5-2(J5)
ON Step input
OFF Pulse input
YES YES
YES
NO
NO
Does the
voltage oscillate
between DC6 and 10V
between control switch
circuit board connector
(CnB) Y (White)
to Z (Black)?
Does the
voltage oscillate
between DC6 and
10V between indoor unit
PCB connector (CNB)
2 (White) to 3
(Black)?
YES
NO
NO
Is there
DC 10.8V
between control
switch circuit board con-
nector (CnB) X
(Red) to Z
(Black)?
Is there
DC 10.8V
between indoor unit
PCB connector (CNB)
1 (Red) to 3
(Black)?
YES
Defective indoor
unit PCB
Power
supply
reset
Is it
normalized?
NO
Unit is normal
(Intrusion of accidental
noise on the control switch
cord)
Defective control
switch PCB
(1)
The control switch wiring
(white) or (black) is broken or
have a defective connection.
Defective control switch
PCB Replacement
Defective indoor unit PCB
Replacement
The control switch wiring (red)
or (black) is broken or have a
defective connection.
1
Error display :
e 1
[Communication error between control switch ~ Indoor unit PCB]
Note (1) If it is normalized by changing PCB, judge the control switch or indoor
unit PCB (Communication error between control switch and unit) is
detective.
• Normal voltage for control switch wiring (DC)
Between X and Z : 10.5 ~ 10.8 V
Between Y and Z : 5 ~ 10.8 V